Fault action 1 Display fault 2 Stop all outputs except water pump Fault handling 1 Check whether the condenser ventilation and heat dissipation are good and whether there is a lack of refrigerant 2 Whether the ambient temperature is higher than 43℃ when cooling and higher than 24℃ when heating 3 Whether the capillary tube is blocked and whether the water pump and water flow are normal when heating 4 Whether the A2 plug and wiring are reliable 5 Check or replace the A2 temperature sensor, check or replace the control main board |